Current Sensing Relays Series
						CMD10AD2U
Lead Time:Â
									Stock								
				Days
Multi-function: Overcurrent, Undercurrent, Band (Window), each with Latching option
5A DPDT
5mA – 100mA, 0.05A – 1 A, and 0.5 – 10A
Adjustable 0.1 – 10 seconds
Adjustable 0 – 10 Sec
Din-rail
function
									Multi-function: Overcurrent, Undercurrent, Band (Window), each with Latching option								
					control voltage
									24-240V AC/DC								
					output:
									5A DPDT								
					CURRENT RANGE
									5mA – 100mA, 0.05A – 1 A, and 0.5 – 10A								
					TRIP DELAY
									Adjustable 0.1 – 10 seconds								
					SENSING DELAY ON POWER
									Adjustable 0 – 10 Sec								
					ENCLOSURE STYLE
									Din-rail								
					$186.84
Description of Function
									Overcurrent monitoring (OVER, OVER+LATCH):
When the monitored current exceeds the value adjusted at the MAX-dial, the 
tripping delay (DELAY) begins (red LED MAX flashes). After the tripping delay 
(DELAY) has expired (red LED MAX illuminated), the output relays switch into off position (yellow LED RELAY not illuminated). The output relays again switch into 
on-position (yellow LED illuminated), when the monitored current falls below the 
value adjusted at the MIN-dial (red LED MAX not illuminated). 
If the fault latch is activated (OVER+LATCH) and the monitored current remains 
above the MAX-value longer than the tripping delay, the output relays remain in the 
off-position even if the monitored current falls below the value adjusted at the MIN dial. After resetting the latch (interrupting and re-applying the control voltage), the 
output relays switch into on-position and a new monitoring cycle begins with the 
delay start-up suppression (START).
Undercurrent monitoring (UNDER, UNDER+LATCH):
When the monitored current falls below the value adjusted at the MIN-dial, the 
tripping delay (DELAY) begins (red LED MIN flashes). After the tripping delay 
(DELAY) has expired (red LED MIN illuminated), the output relays switch into 
off-position (yellow LED not illuminated). The output relays again switch into on position (yellow LED illuminated), when the monitored current exceeds the value 
adjusted at the MAX-dial. 
If the fault latch is activated (UNDER+LATCH) and the monitored current remains 
below the MIN-value longer than the tripping delay, the output relays remain in the 
off-position even if the monitored current exceeds the value adjusted at the MAX dial. After resetting the latch (interrupting and re-applying the control voltage), the 
output relays switch into on-position and a new monitoring cycle begins with the 
delay start-up suppression (START).
Band (Window) Function (BAND, BAND+LATCH):
The output relays switch into on-position (yellow LED RELAY illuminated) when 
the monitored current exceeds the value adjusted at the MIN-dial. When the 
monitored current exceeds the value adjusted at the MAX-dial, the tripping delay 
(DELAY) begins (red LED MAX flashes). After the interval has expired (red LED 
MAX illuminated), the output relays switch into off-position (yellow LED RELAY not 
illuminated). The output relays again switch into on-position (yellow LED RELAY 
illuminated) when the monitored current falls below the value adjusted at the MAX dial (red LED MAX not illuminated). When the monitored current falls below the 
value adjusted at the MIN-dial, the tripping delay (DELAY) begins again (red LED 
MIN flashes). After the delay has expired (red LED MIN illuminated), the output 
relays switch into off-position (yellow LED not illuminated).
If the fault latch is activated (WIN+LATCH) and the monitored current remains 
below the MIN-value longer than the set interval of the tripping delay, the output 
relays remain in the off-position even if the monitored current exceeds the value 
adjusted at the MIN-dial. If the monitored current remains above the MAX-value 
longer than the set interval of the tripping delay, the output relays remain in the off position even if the monitored current falls below the value adjusted at the 
MAX-dial. After resetting the latch (interrupting and re-applying the control
voltage), the output relays switch into on-position and a new monitoring cycle 
begins with the delay of the start-up suppression (START)								
				Function Chart
Product Overview
Features:
									Monitors AC single phase and DC current Overcurrent, undercurrent, band (window) modes Latching output option for all functions Adjustable thresholds and time delays Three color LED indicators 5A DPDT output Universal 24-240V AC/DC control voltage range								
				Enclosure Style:
									Din-rail								
				Configuration / Contact Rating:
									5A@250V AC, 5A@24V DC, B300 Pilot Duty								
				
									5A@250V AC, 5A@24V DC, B300 Pilot Duty								
				Application Information:
									Monitored Current Ranges: 5mA-100mA, 50mA-1A, 0.5A-10A Input Voltage Tolerance: 24 to 240V DC (-20% to +25%); 24 to 240V AC (-15% to +10%) Load (Burden): 4.5VA Current Settings: Pick-up (Threshold): 10-100% ln adjustable throughout monitored current range; Drop-out (Hysteresis): Adjustable from 5 to 95% ln Accuracy: Base accuracy: ≤3% (of maximum scale value); Frequency response: -10% to +5% (48 to 400Hz); Adjustment accuracy: ≤5% (of maximum scale value); Repetition accuracy: ≤2%; Temperature influence: ≤0.05% / °C Maximum Allowable Current: Range: Max Current: 5mA-100mA 800mA 50mA-1A 3A 0.5A-10A 12A Recommended Trip Point Hysteresis: >= 5% (ln) Response Times: Pick-up <= 100 ms, Drop-out Adjustable, 0.1-10s; Sensing Delay on Power-up (START t): Adjustable, 0-10s Life: Mechanical: 20,000,000 operations Full Load: 200,000 operations at 1000VA resistive load. Temperature: Operating: -25o to 55o C (-13o to 131o F) Storage: -25o to 70o C (-13o to 158o F) Indicator LED: Green ON: Control Voltage is applied; Green LED flashes: Start-up suppression delay; Yellow ON: Relay output ON; Red ON: Corresponding threshold exceeded; Red flashes: Tripping delay								
				Approvals:
															
															
															Operations
									Model CMD10AD2U monitors single phase AC and DC current to protect against overcurrent and undercurrent fault conditions. A band (window) function can protect equipment that is required to operate within a maximum and minimum current limit. Each function can be set to operate in latch mode. Separate adjustment dials allow selecting the maximum threshold (MAX), minimum threshold (MIN), tripping delay (Delay), and start-up sensing delay (Start). When the supply voltage V is applied, the output relays switch into on-position (yellow LED illuminated) and the start-up suppression (START) begins (green LED V/t flashes). Changes of the monitored current during this period do not affect the state of the output relay. After the startup suppression (START) has expired, the green LED will flash in an alternating pattern when an invalid MIN setting and MAX setting is selected (MIN must be below MAX)								
				Product Reviews
Do you have experience with this product? Leave us a review!
				
			
			
				Add a review			
		
		
			CMD10AD2U
			
		
					Rating*				
				0/5
				
					* Rating is required				
				
				
			
				Your review			
			
			
				* Review is required			
		
					Name				
				
				
					* Name is required				
			
					Email				
				
				
					* Email is required				
			0.0
Based on 0 reviews
| 5 star | 0% | |
| 4 star | 0% | |
| 3 star | 0% | |
| 2 star | 0% | |
| 1 star | 0% | 
0 of 0 reviews
Sorry, no reviews match your current selections
								