• Power Consumption: Less than 40 VA
• Undervoltage: Adjustable from 75-95% of the line voltage setting. Unit will reset at +3% of the Undervoltage trip setting
• Response Times:
Power Up/Restart After Fault: 1 Second fixed
Drop-out Due to Fault:
Phase Loss & Reversal: 100ms Fixed
Undervoltage: 4 Seconds Fixed
• Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
• Temperature:
Operating:-28° to 65° C (-18° to 149° F)
Storage: -40° to 85° C (-18° to 185° F)
• Mounting: Uses an 8 pin octal socket. Requires a 600V rated socket when used on system voltages greater than 300V such as Macromatic Catalog Number 70169-D
Reset: Automatic upon correction of fault