PMD Series

May not be exact product – for reference only.

PMDU

Lead Time: 

10 Days

Protection

Phase Loss, Phase Reversal, Phase Unbalance, Undervoltage, & Overvoltage

Nominal Voltage

190-500V AC

output

10A DPDT

Time Delay on Fault

0.3-30 Sec

Restart Delay

1-300 Sec

mount

35mm Din-Rail

Setting Adjustment

Analog

Options

None

Monitored Voltage

156-550V AC

$123.89

Description of Function

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. Manual reset is available if an external momentary N.C. switch is connected to terminals 4 and 5. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.

Function Chart

Product Overview

Features:

• Protects against phase loss, phase reversal, phase unbalance, undervoltage, and overvoltage, & rapid cycling
• True RMS voltage measurement ensures accurate sensing across more applications
• Retains fault indication and continues monitoring all voltages even with a lost phase
• Full fault indication on top of unit for easy troubleshooting
• Manual reset option works with external switch to reset the relay from the ouside of enclosure
• Compact 52.5mm wide enclosure for both DIN-rail or panel mount
• 10A DPDT output contacts

Enclosure Style:

52.5mm
Configuration / Contact Rating:
DPDT 10A @ 277V AC/30V DC; 1/2HP @ 120/240V AC (N.O.),1/3HP @ 120/240V AC (N.C.), B300 Pilot Duty, R300 (N.O.)
Application Information:
• Power Consumption: Less than 40 VA
• Undervoltage: Adjustable from 80-95% of the line voltage setting. Unit will reset at +3% of the Undervoltage trip setting
• Overvoltage: Fixed at 110% of the line voltage setting. Unit will reset at 107% of the line voltage setting
• Phase Unbalance: Adjustable from 2-10% unbalance
• Response Times:
Restart: 1-300 seconds adjustable
Drop-out Due to Fault:
Phase Loss and Reversal: 100ms fixed
Undervoltage and Overvoltage: 0.3-30 seconds adjustable
Unbalance:
Normal: 0.3-30 seconds adjustable
Severe (Twice Knob Setting): 0.3-2 seconds.
• Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations Temperature: -28° to 65°C (-18° to 149°F).
• Mounting: Mounts on 35mm DIN-rail or panel-mounted with two #8 screws when DIN-rail clips are fully extended from under the enclosure.
Approvals:

Product Reviews

Do you have experience with this product? Leave us a review!
Add a review
PMDU PMDU
Rating*
0/5
* Rating is required
Your review
* Review is required
Name
* Name is required
0.0
Based on 0 reviews
5 star
0%
4 star
0%
3 star
0%
2 star
0%
1 star
0%
0 of 0 reviews

Sorry, no reviews match your current selections