Protection

Phase Loss, Phase Reversal, Phase Unbalance, Undervoltage, & Overvoltage

Nominal Voltage

190-500V AC

output

5A SPDT + SPNO

Time Delay on Fault

4 Sec

Restart Delay

2 Sec

mount

8-Pin Socket

Setting Adjustment

Analog

Options

None

Monitored Voltage

156-550V AC

$92.38

Description of Function

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.

Function Chart

Product Overview

Features:

• Protects against phase loss, phase reversal, phase unbalance, undervoltage, overvoltage & rapid cycling
• Voltage range of 190-500V-greater range that covers more global applications
• True RMS voltage measurement ensures accurate sensing across more applications
• Retains fault indication and continues monitoring all voltages even with a lost phase
• Full fault indication on top of unit for easy troubleshooting
• 5A SPDT/SPNO output provides isolated contact for alarm circuits

Enclosure Style:

Plug-in
Configuration / Contact Rating:
SPDT + SPNO 5A @ 277V AC / 5A @ 30V DC; 1/3HP @ 120/240V AC, B300
Application Information:
• Power Consumption: Less than 40 VA
• Undervoltage: Fixed at 90% of the line voltage setting. Unit will reset at +3% of the Undervoltage trip setting
• Overvoltage: Fixed at 110% of the line voltage setting. Unit will reset at 107% of the line voltage setting
• Phase Unbalance: Fixed at 6% unbalance
• Response Times:
Restart: 2 seconds fixed
Drop-out Due to Fault:
Phase Loss and Reversal: 100ms fixed
Undervoltage and Overvoltage: 4 seconds fixed
Unbalance:
Normal: 4 seconds fixed
Severe (>12%): 0.25 seconds fixed
• Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
• Temperature:
Operating: -28° to 65°C (-18° to 149°F)
Storage: -40° to 85°C (-40° to 185°F)
• Reset: Automatic upon correction of fault
Approvals:

Product Reviews

Do you have experience with this product? Leave us a review!
Add a review
PMPU-FA8X PMPU-FA8X
Rating*
0/5
* Rating is required
Your review
* Review is required
Name
* Name is required
0.0
Based on 0 reviews
5 star
0%
4 star
0%
3 star
0%
2 star
0%
1 star
0%
0 of 0 reviews

Sorry, no reviews match your current selections