TD-7 Series

May not be exact product – for reference only.

TD-70221

Lead Time: 

7 Days

Function

On Delay

CONTROL VOLTAGE

240V AC

output

10A DPDT

TIMING RANGE

0.05 Sec – 999 Hrs

TIMING RANGE 2

None

MOUNT

8-Pin Socket

Setting Adjustment

Digital

Options

None

REMOTE POTENTIOMETER

None

REMOTE POTENTIOMETER 2

None

$86.65

Description of Function

Upon application of control voltage, the time delay (t) begins. At the end of the time delay (t), the output is energized. Control voltage must be removed to reset the time delay relay & de-energize the output.

Function Chart

Product Overview

Features:

• Pushbutton thumbwheels for digital set of time delay
• 50ms – 999 hour programmable time range
• Uses industry-standard 8 pin octal sockets
• 10A DPDT output contacts
• LED indicates timing mode and time out conditions
• Pilot Duty Rating

Enclosure Style:

Plug-In
Configuration / Contact Rating:
DPDT 10A @ 240V AC / 10A @ 30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.), B300 & R300
Application Information:
• Voltage Tolerance:
AC Operation: +10/-15% of nominal at 50/60 Hz
• Load (Burden): 3 VA
• Setting Accuracy:
Constant Voltage & Temperature: ±0.1% of set time or ±50ms, whichever is greater
Variable Voltage & Temperature: ±1% of set time or ±50ms, whichever is greater
• Repeat Accuracy:
Constant Voltage & Temperature: ±0.1% of set time or ±0.02 seconds, whichever is greater
Variable Voltage & Temperature: ±1% of set time or ±0.02 seconds, whichever is greater
• Reset Time: 0.1 Seconds
• Start-up Time: 0.05 Seconds
• Maintain Function Time: 0.01 Seconds
• Temperature:
Operating: -28° to 65° C (-18° to 149° F)
Storage: -40° to 85° C (-40° to 185° F)
• Insulation Voltage: 2 kV
• Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Approvals:

Operations

Over/Under Voltage Relays provide protection to equipment where either an over or under voltage condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop-out when the operating voltage drops to a level below the preset value.

Adjust the pick-up voltage setting (Umax) between the full range as shown on the product nameplate. Then adjust the drop-out voltage setting (Umin) between 75% and 95% of the pick-up setting. The relay energizes (and the LED is Red) when the monitored voltage is above the pick-up setting for a period longer than the fixed pick-up time delay of 0.5 seconds. The relay de-energizes (and the LED is Green) when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay (t), which is adjustable between 0.1-10 seconds. 

Product Reviews

Do you have experience with this product? Leave us a review!
Add a review
TD-70221 TD-70221
Rating*
0/5
* Rating is required
Your review
* Review is required
Name
* Name is required
0.0
Based on 0 reviews
5 star
0%
4 star
0%
3 star
0%
2 star
0%
1 star
0%
0 of 0 reviews

Sorry, no reviews match your current selections