THR-1 Series
THR-14164-36-31JT
Lead Time:
Function
CONTROL VOLTAGE
output
TIMING RANGE
TIMING RANGE 2
MOUNT
Setting Adjustment
Options
REMOTE POTENTIOMETER
REMOTE POTENTIOMETER 2
$41.88
Description of Function
Function Chart
Product Overview
Features:
• Microprocessor-based design for greater performance & maximum flexibility
• Encapsulated for protection against harsh environments
• 10A SPDT relay output contacts
• Relay common internally connected to pin 2 for easier wiring
• Onboard, adjustable, or fixed time delays from 0.05 seconds to 100 hours
Enclosure Style:
Configuration / Contact Rating:
Application Information:
AC Operation: +10/-15% of nominal at 50/60 Hz
DC Operation: +10/-15% of nominal
• Load (Burden): 2 VA
• Setting Accuracy:
Maximum Setting (Adjustable): +5%, -0%
Minimum Setting (Adjustable): +0%, -50%
Fixed: ±2% or ±50ms, whichever is greater
• Repeat Accuracy: ±0.1% or ±0.04 seconds, whichever is greater
• Reset Time: 0.04 Seconds
• Start-up Time: 0.05 seconds
• Maintain Function Time: 0.01 seconds
• Temperature:
Operating: -28° to 65° C (-18° to 149° F)
Storage: -40° to 85° C (-40° to 185° F)
• Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
• Mounting: Surface with one #8 or #10 screw and a maximum tightening torque of 15 in-lbs
Termination: 0.25″ male quick-connect terminals
Approvals:
Operations
Over/Under Voltage Relays provide protection to equipment where either an over or under voltage condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop-out when the operating voltage drops to a level below the preset value.
Adjust the pick-up voltage setting (Umax) between the full range as shown on the product nameplate. Then adjust the drop-out voltage setting (Umin) between 75% and 95% of the pick-up setting. The relay energizes (and the LED is Red) when the monitored voltage is above the pick-up setting for a period longer than the fixed pick-up time delay of 0.5 seconds. The relay de-energizes (and the LED is Green) when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay (t), which is adjustable between 0.1-10 seconds.