THR-3 Series

May not be exact product – for reference only.

THR-3836U

Lead Time: 

10 Days

Function

Multi-function

CONTROL VOLTAGE

24-240V AC & 12-125V DC

output

10A SPDT

TIMING RANGE

0.1 Sec – 100 Min

TIMING RANGE 2

None

MOUNT

Single Screw Mounting

Setting Adjustment

Analog

Options

None

REMOTE POTENTIOMETER

Consult Factory

REMOTE POTENTIOMETER 2

None

$70.13

Description of Function

THR-3836U products have 4 functions & 4 time ranges built-in: Functions Flasher (OFF) Flasher (ON) Watchdog Single Shot Falling Edge. Please see Knowledge Base Article “Understanding Time Delay Relay Functions” under the Support section for the full descriptions and function charts.

Function Chart

Product Overview

Features:

• Multi-Function: 4 common time delay functions in each one
• Universal Voltage: 24-240VAC & 12-125VDC
• Time Ranges: 0.1 Sec to 100 Minutes Onboard & remote adjust of time delay
• Onboard & remote adjust of time delay
• Cost effective design & compact 2″ x 2″ enclosure
• Encapsulated for protection against harsh environments
• 10A SPDT relay output contacts can handle most pilot duty & fractional HP loads

Enclosure Style:

Encapsulated
Configuration / Contact Rating:
SPDT 10A @ 240VAC / 7A @ 28VDC, 1/4 HP @ 120VAC (N.O.)
Application Information:
• Voltage Tolerance:
AC Operation: +10/-15% of nominal at 50/60 Hz
DC Operation: +10/-15% of nominal
• Load (Burden): 2 VA
• Setting Accuracy:
Maximum Setting (Adjustable): +5%, -0%
Minimum Setting (Adjustable): +0%, -50%
• Repeat Accuracy: ±0.1% or ±0.04 seconds, whichever is greater
• Reset Time:
Non-Triggered Function: 0.1 Seconds
Triggered Functions: 0.04 Seconds
• Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
• Temperature:
Operating: -28° to 65°C (-18° to 149°F)
Storage: -40° to 85°C (-40° to 185°F)
• Mounting: Surface with one #8 or #10 screw and a maximum tightening torque of 15 in-lbs
• Termination: 0.25″ male quick-connect terminals
Approvals:

Operations

Over/Under Voltage Relays provide protection to equipment where either an over or under voltage condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop-out when the operating voltage drops to a level below the preset value.

Adjust the pick-up voltage setting (Umax) between the full range as shown on the product nameplate. Then adjust the drop-out voltage setting (Umin) between 75% and 95% of the pick-up setting. The relay energizes (and the LED is Red) when the monitored voltage is above the pick-up setting for a period longer than the fixed pick-up time delay of 0.5 seconds. The relay de-energizes (and the LED is Green) when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay (t), which is adjustable between 0.1-10 seconds. 

Product Reviews

Do you have experience with this product? Leave us a review!
Add a review
THR-3836U THR-3836U
Rating*
0/5
* Rating is required
Your review
* Review is required
Name
* Name is required
0.0
Based on 0 reviews
5 star
0%
4 star
0%
3 star
0%
2 star
0%
1 star
0%
0 of 0 reviews

Sorry, no reviews match your current selections