TR-6 Series

May not be exact product – for reference only.

TR-60626

Lead Time: 

7 days

Function

True Off Delay

CONTROL VOLTAGE

12V DC

output

10A DPDT

TIMING RANGE

50 Ms – 30 Min

TIMING RANGE 2

None

MOUNT

8-Pin Socket

Setting Adjustment

Analog

Options

None

REMOTE POTENTIOMETER

None

REMOTE POTENTIOMETER 2

None

$115.54

Description of Function

Upon application of control voltage, the output is energized. When the input voltage is removed, the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Input voltage must be applied for a minimum of 0.5 seconds to assure proper operation. Any application of the control voltage during the time delay (t) will reset the time delay. No external trigger is required.

Function Chart

Product Overview

Features:

• Each unit has 8 timing ranges built-in covering 0.05 seconds-30 minutes
• Selecting a range is easy using a rotary switch (no math is required or DIP switches to set)
• Uses industry-standard 8 pin octal sockets
• 10A output contacts can handle most pilot duty & fractional HP loads

Enclosure Style:

Plug-In
Configuration / Contact Rating:
DPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.),1/3HP @ 120/240V AC (N.C.), B300 & R300; AC15 & DC18
Application Information:
• Voltage Tolerance:
AC Operation: +10%/-15% of nominal at 50/60Hz
DC Operation: +10%/-15% of nominal
• Load (Burden): 2 VA, These products draw a brief inrush current on power-up of 1A to charge the internal circuitry
• Setting Accuracy:
Maximum Setting (Adjustable): +5%, -0%
Minimum Setting (Adjustable): +0%, -50%
• Repeat Accuracy: +0.1% or +50ms, whichever is greater
• Reset Time: 0.1 Seconds
• Start-up Time: 0.05 Seconds
• Maintain Function Time: 0.01 Seconds
• Temperature:
Operating: -28° to 65° C (-18° to 149° F)
Storage: -40° to 85° C (-40° to 185° F)
• Life:
Mechanical: 2,000,000 operations
Full Load: 100,000 operations
Approvals:

Operations

Over/Under Voltage Relays provide protection to equipment where either an over or under voltage condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop-out when the operating voltage drops to a level below the preset value.

Adjust the pick-up voltage setting (Umax) between the full range as shown on the product nameplate. Then adjust the drop-out voltage setting (Umin) between 75% and 95% of the pick-up setting. The relay energizes (and the LED is Red) when the monitored voltage is above the pick-up setting for a period longer than the fixed pick-up time delay of 0.5 seconds. The relay de-energizes (and the LED is Green) when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay (t), which is adjustable between 0.1-10 seconds. 

Product Reviews

Do you have experience with this product? Leave us a review!
Add a review
TR-60626 TR-60626
Rating*
0/5
* Rating is required
Your review
* Review is required
Name
* Name is required
0.0
Based on 0 reviews
5 star
0%
4 star
0%
3 star
0%
2 star
0%
1 star
0%
0 of 0 reviews

Sorry, no reviews match your current selections